Line 4: Line 4:
  
 The Victron system monitor, the [[https://www.victronenergy.com/panel-systems-remote-monitoring/color-control|Color Control GX]] includes [[ccgx:ccgx_fronius|built-in Fronius monitoring]]. The Victron system monitor, the [[https://www.victronenergy.com/panel-systems-remote-monitoring/color-control|Color Control GX]] includes [[ccgx:ccgx_fronius|built-in Fronius monitoring]].
 +
 +{{:ac_coupling:ccgx_devicelist_fronius.png?direct|}}
 +{{:ac_coupling:ccgx_hub4_overview_froniusicon.png?direct|}}
 +
  
 ===== Frequency shifting ===== ===== Frequency shifting =====
Line 9: Line 13:
 To make sure that the Fronius PV inverter works well with Victron inverter/chargers, both must be configured with the right 'frequency shift settings': To make sure that the Fronius PV inverter works well with Victron inverter/chargers, both must be configured with the right 'frequency shift settings':
   * The Fronius PV Inverter must be set to Setup MG, short for Micro-Grid.    * The Fronius PV Inverter must be set to Setup MG, short for Micro-Grid. 
-  * The Victron inverter/charger must be loaded with either the PV Inverter support Assistant or the Hub-2 v3 Assistant. +  * For off-grid systems, load the Multi or Quattro with the PV Inverter support Assistant 
 +  * For on-grid / energy-storage systems, load the Multi or Quattro with the ESS Assistant. Read information about ESS in the [[ess:design-installation-manual|]].
  
-And the [[ac_coupling:start|1:1 rule]] must be adhered to.+And the [[ac_coupling:start|1:limit rule]] must be adhered to.
  
 ===== Fronius / Victron specifics ===== ===== Fronius / Victron specifics =====
  
-This is a very easy setup. The Fronius Setup MG has been developed in close cooperation with Victron Energy. During commissioning, set the PV Inverter to Setup MG 50, or Setup MG 60 for 60 Hz systems. Everything is then pre-configured. The Setup MG settings match the default Victron Assistant settings.+This is a very easy setup. The Fronius Setup Microgrid has been developed in close cooperation with Victron. During commissioning, set the PV Inverter to Setup MG50 (or Setup MG60 for 60 Hz systems). Everything is then pre-configured. The Setup MG settings match the default Victron Assistant settings.
    
-Compatible inverters are: +**Compatible ROW inverters** (for "European type AC grid"are: 
-  * Fronius IG Plus V (1~, 2~, 3~, 2.5 kW up to 12 kW) -> from IGF 5.0.66 on with settings according to the VICTRON recommendations. +  * Fronius Primo (1~, 3 kW up to 8.2 kW) -> Software //fro27140.upd// or higher (see FAQ Q5!
-  * Fronius Galvo (1~, 1.5 kW up to 3.1 kW-> use latest FW +  * Fronius Symo (3~, 3 kW up to 20 kW) -> Software //fro27140.upd// or higher (see FAQ Q5!) 
-  * Fronius Symo (3~, 3 kW up to 20 kW) -> use latest FW +  * Fronius Eco (3~, 25 kW or 27 kW) -> Software //fro27140.upd// or higher (see FAQ Q5!) 
-  * Fronius Primo (1~, kW up to 8.2 kW) -> use latest FW +  * Fronius Agilo (3~, 75 kW up to 100 kW) -> Software //update19.tl// or higher 
-  * Fronius Eco (3~, 25 kW up to 27 kW) -> use latest FW +  * Fronius IG Plus V (1~, 2~, 3~, 2.5 kW up to 12 kW) -> from //IGF 5.0.66// on with settings according to the Victron recommendations
-  * Fronius Agilo (3~, 75 kW up to 100 kW) -> use latest FW+
  
-Recommended for new systems are the Symo or Eco inverters for 3~ systems and Primo inverters for 1~ systemsDo note that these two products are transformerless and therefore PV-Modules that need to be grounded cannot be connected.+For new systems the Fronius Symo and Fronius Eco inverters are recommended for 3~ applications. The Fronius Primo inverters are recommended for 1~ applicationsPlease note that all these inverters are transformerless and therefore PV-Modules that require pole-grounding (on the Plus or Minus pole) cannot be connected.
  
-When the PV modules need to be grounded, use inverters from the IG Plus V series or Fronius Galvo inverters.+The use of Fronius Galvo inverters is not recommended anymore for new applications - the Fronius Primo is the best substitute and offers higher efficiency, wider DC voltage range and two MPP trackers. 
 + 
 +**Compatible UL inverters** (for "US type AC grid") are: 
 +  * Fronius Primo UL (1~, 3.8 kW up to 15 kW) -> Software //fro27470.upd// or higher (see FAQ Q5!) 
 +  * Fronius Symo 10-24 480V (3~, 10 kW up to 24 kW) -> Software //fro27140.upd// or higher (see FAQ Q5!) 
 +  * Fronius Symo 10-15 208-240V (3~, 10 up to 15 kW) -> Software //fro27140.upd// or higher (see FAQ Q5!) 
 + 
 +For the UL inverters, some more Microgrid Setups are available (e.g. for connection with Neutral conductor or without). Also the UL inverters can be used in 60Hz as well as in 50Hz applications. More information can be found in the user manuals.
  
 When setting up a system, always update both the Fronius and the Victron devices to their latest firmware versions. For the latest Fronius firmware and information how to update use this link: When setting up a system, always update both the Fronius and the Victron devices to their latest firmware versions. For the latest Fronius firmware and information how to update use this link:
 [[http://www.fronius.com/cps/rde/xchg/SID-0E6A6973-2D12EBA2/fronius_international/hs.xsl/83_20347_ENG_HTML.htm#.VouMJOb9XxQ|Fronius firmware update]] [[http://www.fronius.com/cps/rde/xchg/SID-0E6A6973-2D12EBA2/fronius_international/hs.xsl/83_20347_ENG_HTML.htm#.VouMJOb9XxQ|Fronius firmware update]]
  
-===== Setting up the Fronius with MG 50/60 =====+===== Setting up the Fronius with Setup MG50/MG60 =====
  
 When not pre-ordered with a MicroGrid setup, follow these steps: When not pre-ordered with a MicroGrid setup, follow these steps:
Line 45: Line 56:
   - Go to the tab Assistants: \\ {{:ac_coupling:add_assistant.png?nolink&}}   - Go to the tab Assistants: \\ {{:ac_coupling:add_assistant.png?nolink&}}
   - Add one of the Assistants that regulate output frequency:   - Add one of the Assistants that regulate output frequency:
-      - Self-consumption Hub-2 v2 +      - [[ess:design-installation-manual|ESS Assistant]]
-      - Self-consumption Hub-2 v3+
       - PV Inverter support       - PV Inverter support
   - Note that it is not necessary to change the default settings in the Assistant. \\ {{:ac_coupling:8b249443cd6d2a5632b07998773a1e6d.png?nolink&}} \\   - Note that it is not necessary to change the default settings in the Assistant. \\ {{:ac_coupling:8b249443cd6d2a5632b07998773a1e6d.png?nolink&}} \\
Line 52: Line 62:
 \\ \\
  
-More information on adding Assistans is [[assistants:how_to_add_and_configure_an_assistant|here]]+Table for settings for 50Hz and 60Hz frequency 
-===== Frequently asked questions =====+| ** State ** | ** 50Hz ** | ** 60Hz ** |. | 
 +| Start| 51.0 | 60.2|Hz| 
 +| Minimum| 52.7 | 62.7|Hz| 
 +| Disconnect| 53.0 | 63.0|Hz| \\
  
-=== Why doesn't the frequency settings in the Multi and the Fronius need to be the same? ===+More information on adding Assistants is [[assistants:how_to_add_and_configure_an_assistant|here]]. 
 + 
 +===== Remote system monitoring ===== 
 + 
 +The Victron system can be monitored through Victron VRM Portal if a [[https://www.victronenergy.com/panel-systems-remote-monitoring/color-control|Color Control GX]] is present at the site. 
 +The Fronius PV inverter data can be [[ccgx:ccgx_fronius|integrated into the Color Control GX]]  and therefore also in the VRM portal. 
 +So the VRM portal is the recommended monitoring platform also for AC-coupled installations. 
 +  
 +However, also Fronius offers an equivalent monitoring solution. The Fronius portal is called Fronius Solar.web. The PV system data can be transfered to the portal if the inverter is equipped with a Datamanager 1.0 or Datamanager 2.0. 
 + 
 +The usage of both portals in parallel is possible. 
 + 
 +A video instruction how to set up the Datamanager 2.0 + Solar.web can be found [[https://youtu.be/u_DX7PmHPXQ|here]]. 
 + 
 +===== Zero Feed-in ===== 
 + 
 +It is possible to make a Zero feed-in system with Victron & Fronius. The Venus device will the control the Fronius output power. See the [[ess:design-installation-manual|ESS manual]], chapter 4.3.11 Fronius Zero feed-in for details. 
 +===== Frequently Asked Questions ===== 
 + 
 +==== Q1 Why doesn't the frequency settings in the Multi and the Fronius need to be the same? ====
  
 The first two frequencies do not need to be the same since the Multi actively regulates.  The first two frequencies do not need to be the same since the Multi actively regulates. 
  
-=== I have an Fronius IG inverter (not Plus), can that work? ===+==== Q2 I have an Fronius IG inverter (not Plus), can that work? ====
 No, the IG inverters cannot be made to work in a MicroGrid system. The appropriate substitute for an IG 30 is the GALVO 2.5-1 or an IG Plus 25V-1 (depending on the desired DC voltage range). No, the IG inverters cannot be made to work in a MicroGrid system. The appropriate substitute for an IG 30 is the GALVO 2.5-1 or an IG Plus 25V-1 (depending on the desired DC voltage range).
  
 +==== Q3 The system is locked to 53 Hz and does not resume ====
 +See [[:assistants:pv-inverter-support#q1_the_system_is_locked_to_53_hz_and_does_not_resume|here]].
 +==== Q4 Can I use the Fronius Smart Meter? ====
 +
 +That depends on the type of system and software configuration.
 +
 +A Fronius Smart Meter can be used in these two situations:
 +
 +  - when used only for reporting to Solarweb
 +  - when used for limiting export, in a system where the Victron system is not configured as an ESS system.
 +
 +The Fronius Smart-Meter can not be used for the Fronius built-in export limiting feature when part of a Victron ESS system. Instead, use the Victron ESS Fronius Zero-feed in feature, see chapter 4.3.11, Fronius Zero Feed-in, in the [[ess:design-installation-manual|ESS manual]].
 +
 +
 +==== Q5 How can I get the Fronius firmware that improves flickering? ====
 +
 +Fronius has a special firmware available, on request, that fixes light flickering issues that occur on certain installations under certain circumstances.
 +
 +For Fronius PV inverters produced after 2018-week 16, contain the flicker-fix already straight from production.
 +
 +To update earlier and/or already installed PV Inverters, contact Fronius Tech Support for the file. The required file is fro29130.upd. Which works for all snap-inverter models (Primo, Symo and Eco). There is no, and will be no, fix available for Fronius Galvos.
 +