ac_coupling:fronius

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
ac_coupling:fronius [2024-10-09 07:42] guy_stewartac_coupling:fronius [2025-05-26 10:31] (current) iburger
Line 63: Line 63:
       - [[ess:design-installation-manual|ESS Assistant]]       - [[ess:design-installation-manual|ESS Assistant]]
       - PV Inverter support       - PV Inverter support
-  - Note that it is not necessary to change the default settings in the Assistant. \\ {{:ac_coupling:ess_frequency_settings.png?nolink&}} \\+  - Carefully review the settings in the Assistant, as this was changed in later Fronius firmware versions. See tables below. \\ {{:ac_coupling:ess_frequency_settings.png?nolink&}} \\
   - Complete the rest of the Assistant and write the new settings to the MultiPlus or Quattro.   - Complete the rest of the Assistant and write the new settings to the MultiPlus or Quattro.
 \\ \\
  
-Table with general suggested settings for 50Hz and 60Hz frequency+Suggested suggested settings for frequency (Fronius firmware before fro35020)
 | ** State ** | ** 50Hz ** | ** 60Hz ** |. | | ** State ** | ** 50Hz ** | ** 60Hz ** |. |
 | Start| 50.2 | 60.2|Hz| | Start| 50.2 | 60.2|Hz|
 | Minimum| 52.7 | 62.7|Hz| | Minimum| 52.7 | 62.7|Hz|
 | Disconnect| 53.0 | 63.0|Hz| \\ | Disconnect| 53.0 | 63.0|Hz| \\
 +
 +Suggested suggested settings for frequency (Fronius firmware after fro35020)
 +| ** State ** | ** 50Hz ** | ** 60Hz ** |. |
 +| Start| 50.2 | 60.2|Hz|
 +| Minimum| 53.1 | 63.1|Hz|
 +| Disconnect| 53.5 | 63.5|Hz| \\
 +
  
 Note that although the MG50 for instance has a higher start frequency of 51Hz, there is no real drawback using the proposed value of 50.2Hz. The system will just increase the frequency until the PV inverter regulation kicks in. The value of 50.2Hz will work with a broader range of PV inverters/grid codes. Note that although the MG50 for instance has a higher start frequency of 51Hz, there is no real drawback using the proposed value of 50.2Hz. The system will just increase the frequency until the PV inverter regulation kicks in. The value of 50.2Hz will work with a broader range of PV inverters/grid codes.
ac_coupling/fronius.txt · Last modified: by iburger