ac_coupling:fronius
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revision | |||
ac_coupling:fronius [2024-10-09 07:42] – guy_stewart | ac_coupling:fronius [2025-05-26 10:31] (current) – iburger | ||
---|---|---|---|
Line 63: | Line 63: | ||
- [[ess: | - [[ess: | ||
- PV Inverter support | - PV Inverter support | ||
- | - Note that it is not necessary to change | + | - Carefully review |
- Complete the rest of the Assistant and write the new settings to the MultiPlus or Quattro. | - Complete the rest of the Assistant and write the new settings to the MultiPlus or Quattro. | ||
\\ | \\ | ||
- | Table with general | + | Suggested |
| ** State ** | ** 50Hz ** | ** 60Hz ** |. | | | ** State ** | ** 50Hz ** | ** 60Hz ** |. | | ||
| Start| 50.2 | 60.2|Hz| | | Start| 50.2 | 60.2|Hz| | ||
| Minimum| 52.7 | 62.7|Hz| | | Minimum| 52.7 | 62.7|Hz| | ||
| Disconnect| 53.0 | 63.0|Hz| \\ | | Disconnect| 53.0 | 63.0|Hz| \\ | ||
+ | |||
+ | Suggested suggested settings for frequency (Fronius firmware after fro35020) | ||
+ | | ** State ** | ** 50Hz ** | ** 60Hz ** |. | | ||
+ | | Start| 50.2 | 60.2|Hz| | ||
+ | | Minimum| 53.1 | 63.1|Hz| | ||
+ | | Disconnect| 53.5 | 63.5|Hz| \\ | ||
+ | |||
Note that although the MG50 for instance has a higher start frequency of 51Hz, there is no real drawback using the proposed value of 50.2Hz. The system will just increase the frequency until the PV inverter regulation kicks in. The value of 50.2Hz will work with a broader range of PV inverters/ | Note that although the MG50 for instance has a higher start frequency of 51Hz, there is no real drawback using the proposed value of 50.2Hz. The system will just increase the frequency until the PV inverter regulation kicks in. The value of 50.2Hz will work with a broader range of PV inverters/ |
ac_coupling/fronius.txt · Last modified: by iburger