Table of Contents
Cegasa E/Scal 6
Manufacturer links
Use with the HS19 (650 - 1000 V DC)
Full product specifications (unverified, from manufacturer datasheet)
Compatibility status
Setup guide
Cegasa E/Scal 6
Manufacturer links
Product page:
Cegasa E/Scal 6
Datasheet:
TDS E/Scal 6 (English, Nov 2025)
Use with the HS19 (650 - 1000 V DC)
Modules per stack:
13 - 15
(the product allows 3 - 15, but fewer than 13 modules sits below the HS19 input range)
Usable voltage range:
676 - 940 V
Capacity:
75 - 86 kWh
per stack
derived from datasheet per-module voltages, not yet verified
Full product specifications (unverified, from manufacturer datasheet)
Module: 57.6 V nominal, 5.76 kWh (~100 Ah)
Up to 4 strings in parallel (max 60 modules, 345 kWh)
Recommended current 50 A, max 63 A continuous, 100 A peak (<1 min)
Note: E/Scal 6 is the renamed continuation of the E/Scal HV; certificates may still reference the old name
Compatibility status
Test status: tested and running in field tests
FDCan support: yes, but needs verification
Setup guide
Setup instructions to be written.